Key Features

  • Single output, ON/OFF or PID with autotuning
  • Cooling/heating and humidifying/dehumidifying, selectable
  • Main output: changeover relay or external SSR control
  • PTC1000, NTC10K or 0-1V (rH%) input, model dependent
  • Available with various mains power-supply options (12Vac/dc, 230Vac, 115Vac)
  • TTL or RS485 serial port with selectable ASCII/RTU protocol
  • Reliable mechanical keypad

Product range

Technical Data
LTR-5T LTR-5C LTR-5A
Inputs Type PTC1000 NTC10K 0-1V (rH%)
Range -50÷150°C / -60÷300°F -40÷125°C / -40÷260°F 0..99% r.H.
Accuracy* <±0.3°C -50..140°C; ±1°C
out of that range
<±0.3°C -40..100°C; ±1°C
out of that range
<±0.7% r.H. in the
measuring range
Outputs OUT1 (Relay) 3.6 FLA, 21.6 LRA @ 240Vac; 16A resistive
OUT1 (External SSR control) 15mA 12Vdc
Technical specifications Power supply LTR-5…D  12Vac/dc ±10%, 2W
LTR-5…E  230Vac ±10%, 50/60Hz, 2W
LTR-5…U  115Vac ±10%, 50/60Hz, 2W
Front protection IP54 (with gasket)
Buzzer No
Real Time Clock battery No
Dimensions 77 x 35 x 77 mm
Panel-cutout 71 x 29 mm (WxH)
Environment conditions Operating temperature & humidity -10… +50°C; 15%… 80% rH
Conformity Marks CE
Use with flammable refrigerants No

Documentation

Access datasheets, manuals, software and technical resources of CD5.

355 KB
Technical Data LTR-5

Updated 18/12/2025

EN
.PDF
821 KB
Instructions for use LTR-5

Updated 12/06/2026

.PDF